Filter









Filter
30
Results

VIALED TUBE

  • Available with lenses for standard or high ceilings
  • New high-brightness LED
  • High lighting performances
  • Aluminum casing design
  • Symmetrical and asymmetrical lenses included
IP42

List of results, divided by function

LIGHTING PERFORMANCE H 3 M - STANDARD LENSES
 
ASYMMETRICAL
Individual installation

Escape routes

Max distance covered: 20 m > 1 lx

ASYMMETRICAL
Multiple installation

Escape routes

Max distance covered: 41,6 m > 1 lx
Max spacing between luminaires: 21,6 m > 1 lx

SYMMETRICAL
Individual installation

Anti-panic areas, emergency exits, stairs, first aid areas, fire-fighting equipment, etc.

Surface covered: 131 m2 > 0,5 lx

Values calculated on floors without reflections.

LIGHTING PERFORMANCE H10 M - LARGE HEIGHT LENSES
 
ASYMMETRICAL
Individual installation

Escape routes

Max distance covered: 21 m > 1 lx

ASYMMETRICAL
Multiple installation

Escape routes

Max distance covered: 46,4 m > 1 lx
Max spacing between luminaires: 25,3 m > 1 lx

SYMMETRICAL
Individual installation

Anti-panic areas, emergency exits, stairs, first aid areas, fire-fighting equipment, etc.

Surface covered: 119 m2 > 0,5 lx

Values calculated on floors without reflections.

TECHNICAL FEATURES

  • High-efficiency lighting LED
  • Patented optics
  • Lens optimized for best luminous flux
  • Maximum battery recharge time: 12h
  • Compliant with European standards EN 60598-1, EN 60598-2-22

INSTALLATION

Vialed Tube can be installed on ceilings.

It can also be installed in suspension, using optional accessories.